Related Materials: Policy on UFGS Changes and Revisions
Below is a listing of the Revisions and Changes made to UFGS Sections for each quarterly release.
To view a list for a specific UFGS Release, select the UFGS release date from the 'Release' drop-down and click 'Apply'.
To view a list of all the revisions and changes made to a specific UFGS Section, select 'Any' from the "Release' drop down, type the Section number into the Search bar and select the Section to view, then click 'Apply'.
After clicking 'Apply', you can PRINT REPORT, which will include the nature of the change/revision.
To view the complete detailed history of all the revisions and changes made to a UFGS Section, click on the Section title.
KEY | PREPARING ACTIVITY (PA) | A Army | N Navy | F Air Force | S NASA |
---|---|---|---|---|---|
ACTION | N New | R Revision | C Change | D Deletion |
Release | PA | UFGS Section | Date |
Action![]() |
Change # | Nature of Change or Revision |
---|---|---|---|---|---|---|
Aug-2018 | N | UFGS 23 54 19 Building Heating Systems, Warm Air | Nov-2008 | C | 2 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 23 64 00 Packaged Water Chillers, Absorption Type | Nov-2016 | C | 2 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 23 64 10 Water Chillers, Vapor Compression Type | Nov-2016 | C | 2 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 23 65 00 Cooling Towers and Remote Evaporatively-Cooled Condensers | Nov-2016 | C | 2 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 23 69 00.00 20 Refrigeration Equipment for Cold Storage | Jul-2006 | C | 2 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 23 76 00.00 20 Evaporative Cooling System | Jul-2006 | C | 2 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 23 81 00.00 20 Unitary Air Conditioning Equipment | Nov-2009 | C | 4 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 23 81 23.00 20 Computer Room Air Conditioning Units | Feb-2010 | C | 3 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 23 81 47 Water-Loop and Ground-Loop Heat Pump Systems | Aug-2008 | C | 4 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 23 82 00.00 20 Terminal Heating Units | Feb-2016 | C | 1 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 26 11 13.00 20 Primary Unit Substations | Apr-2007 | C | 2 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 26 12 19.10 Three-Phase, Liquid-Filled Pad-Mounted Transformers | May-2017 | C | 2 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 26 12 21 Single-Phase Pad-Mounted Transformers | May-2017 | C | 1 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 26 29 23 Adjustable Speed Drive (ASD) Systems Under 600 Volts | Apr-2006 | C | 1 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 26 33 53.00 20 Uninterruptible Power Supply (UPS) | Apr-2008 | C | 1 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 26 55 80 Surgical, Procedure and Exam Lighting Fixtures | Apr-2006 | C | 1 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | N | UFGS 26 56 00 Exterior Lighting | May-2013 | C | 1 | Statements added to specify LED compatible photocell when used with LED light fixtures; Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Apr-2008 | A | UFGS 14 21 23 Electric Traction Passenger Elevators | Jul-2007 | C | Preparing Activity Changed from NAVFAC to USACE | |
Aug-2018 | S | UFGS 08 41 13 Aluminum-Framed Entrances and Storefronts | Aug-2018 | C | 1 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | S | UFGS 12 36 00 Countertops | Aug-2018 | C | 2 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Aug-2018 | A | UFGS 05 21 00 Steel Joist Framing | May-2015 | C | 1 | Sustainability updates required to coordinate with the Federal Codes and DoD policies and procedures. |
Nov-2018 | A | UFGS 01 78 00 Closeout Submittals | Aug-2011 | C | 4 | Deleted reference to NFAS Clause. Added Sustainable Materials certification reporting requirements. |
Nov-2018 | A | UFGS 04 20 00 Unit Masonry | Nov-2015 | C | 1 | Added Single-Wythe Exterior Wall CMU Flashing System, requirements for tooled joints, and note for load-bearing unit types. |
Nov-2018 | A | UFGS 06 17 19 Cross-Laminated Timber | Nov-2016 | C | 1 | Added recommendation not to use CLT in humid or ESC locations C4 and C5. |
Nov-2018 | A | UFGS 06 41 16.00 10 Plastic-Laminate-Clad Architectural Cabinets | Aug-2010 | C | 1 | Updated reference in response to CCR 6899. |
Nov-2018 | A | UFGS 09 24 23 Cement Stucco | Aug-2017 | C | 2 | Added requirements for accessories, hangers, and wires, in high humidity and ESC C3-C5 locations, and straps or rods in locations subject to violent storms. |
Nov-2018 | A | UFGS 09 51 00 Acoustical Ceilings | Aug-2017 | C | 2 | Added requirements for suspension systems materials in high humidity and ESC C3-C5 locations. |
Nov-2018 | A | UFGS 09 64 23 Wood Parquet Flooring | Aug-2016 | C | 3 | Added note to use termite treated wood in termite prone areas. |
Nov-2018 | A | UFGS 09 64 29 Wood Strip and Plank Flooring | Aug-2016 | C | 2 | Added note to use termite treated wood flooring in termite prone areas. |
Nov-2018 | A | UFGS 09 66 13 Portland Cement Terrazzo Flooring | Aug-2016 | C | 2 | Added requirement prohibiting use of coral, dolomite or limestone aggregates in setting bed. |
Nov-2018 | A | UFGS 10 14 00.10 Exterior Signage | Aug-2017 | C | 1 | Added note for material requirements of exterior sheeting panels, brackets, posts, fasteners, and hardware in ESC C3-C5 locations. |
Nov-2018 | A | UFGS 10 14 00.20 Interior Signage | Aug-2017 | C | 2 | Added note and material requirements for panels, brackets, fasteners, and hardware for unoccupied spaces and high humidity and ESC C4-C5 locations and for standard room signs in humid and C3-C5 locations. |
Nov-2018 | A | UFGS 10 21 13 Toilet Compartments | Aug-2017 | C | 2 | Added note and requirement for partitions. Added requirement for panels, brackets, fasteners and hardware in unconditioned spaces and humid and ESC C4-C5 locations. |
Nov-2018 | A | UFGS 12 21 00 Window Blinds | Aug-2017 | C | 2 | Added requirement for materials in humid and ESC C3-C5 locations. |
Nov-2018 | A | UFGS 12 35 70 Healthcare Casework | Aug-2016 | C | 2 | Added note for drawer bottoms, plastic laminate covered cabinet doors, and non-ferrous metal fasteners, fittings, and hardware. Added note prohibiting use of particle board for countertops in high humidity and C3-C5 locations. |
Nov-2018 | A | UFGS 12 50 00.13 10 Furniture and Furniture Installation | Aug-2017 | C | 1 | Changed title of paragraph 2.3.1 in response to CCR 6726. |
Nov-2018 | A | UFGS 13 49 10 X-Ray Shielding | Feb-2009 | C | 1 | Updated reference in response to CCRs 6683 and 6685. |
Nov-2018 | A | UFGS 32 17 23 Pavement Markings | Aug-2016 | C | 5 | Updated/replaced references in response to CCR 6522. |
Nov-2018 | N | UFGS 00 22 13.00 20 Supplementary Instructions to Offerors | Feb-2014 | C | 3 | Deleted requirement for Azores excess shipping cost provisions. |
Nov-2018 | N | UFGS 01 14 00 Work Restrictions | Nov-2011 | C | 6 | Changed tailoring tags from NAVFAC PAC to NAVFAC HI based on CCRs, removed outdated information for Naval Shipyard Pearl Harbor, HI, and added personnel security requirements for use in secure or controlled areas. |
Nov-2018 | N | UFGS 01 32 17.00 20 Cost-Loaded Network Analysis Schedules (NAS) | May-2018 | C | 1 | Corrected notes and paragraphs, for DB and DBB, on Baseline NAS submittals and requirements. |
Nov-2018 | N | UFGS 03 30 00 Cast-In-Place Concrete | May-2014 | C | 4 | Added note to use UFGS 03 31 29 or UFGS 03 31 30 in ESC C4 and C5 locations or where deicing salts. |
Nov-2018 | N | UFGS 03 31 29 Marine Concrete with Service Life Modeling | Aug-2012 | C | 2 | Added notes to direct use of this section and Type II and V Portland cement in ESC C4 and C5 locations and where deicing salts used on structure, note for coral aggregates, and note for water reducing. |
Nov-2018 | N | UFGS 05 12 00 Structural Steel | Aug-2018 | C | 1 | Added note for shop primer requirements in exterior locations or areas open to the exterior. |
Nov-2018 | N | UFGS 06 10 00 Rough Carpentry | Aug-2016 | C | 2 | Added notes for requirement of preservative treatment and hot-dip galvanized rough hardware in ESC C3 thru C5 and humid locations, and not to use particle board or OSB in C4 and C5 and humid locations. |
Nov-2018 | N | UFGS 06 20 00 Finish Carpentry | Aug-2016 | C | 2 | Added notes to not use particleboard or hardboard siding in humid or ESC C4 and C5 locations. |
Nov-2018 | N | UFGS 07 22 00 Roof and Deck Insulation | Feb-2016 | C | 3 | Added notes to consider use of polystyrene as a roof insulation in humid or ESC C3-C5 locations and not to use wood fiberboard in humid or ESC C4-C5 locations. |
Nov-2018 | N | UFGS 07 41 13 Metal Roof Panels | May-2011 | C | 2 | Added notes for gauge requirements of Aluminum and Steel Sheet Panels in humid and ESC C3-C5 locations. |
Nov-2018 | N | UFGS 07 51 13 Built-Up Asphalt Roofing | May-2012 | C | 2 | Added notes restricting use of coral gravel in humid and ESC C3-C5 locations and gravel surface cap sheet in humid and ESC C4-C5 locations. |
Nov-2018 | N | UFGS 07 60 00 Flashing and Sheet Metal | May-2017 | C | 2 | Added notes for flashing requirements, lead sheet, thickness of aluminum alloy sheet and plate, and fasteners in humid or ESC C3-C5 locations and nailing in ESC C4-C5 locations. |
Nov-2018 | N | UFGS 07 61 15.00 20 Aluminum Standing Seam Roofing | Aug-2016 | C | 2 | Added note for use of coated alclad in ESC C3-C5 locations. |
Nov-2018 | N | UFGS 07 92 00 Joint Sealants | Aug-2016 | C | 3 | Added sealant requirements with ambient temperatures that exceed 43.33 degrees C (110 degrees F). |
Nov-2018 | N | UFGS 08 11 13 Steel Doors and Frames | Feb-2010 | C | 3 | Added note for door louvers and exterior screens in humid or ESC C3-C5 locations. |
Nov-2018 | N | UFGS 08 11 16 Aluminum Doors and Frames | May-2017 | C | 2 | In paragraph "Finishes," defined corrosive atmospheres in terms of ISO 9223 ESC C3-C5, and humid locations in terms of ASHRAE 90.1. |
Nov-2018 | N | UFGS 08 51 13 Aluminum Windows | May-2011 | C | 4 | Added note for finish requirements in humid and ESC C3-C5 locations. |
Nov-2018 | N | UFGS 08 51 23 Steel Windows | Aug-2011 | C | 4 | Added note restricting use of steel windows in humid and ESC C3-C5 locations. |
Nov-2018 | N | UFGS 08 52 00 Wood Windows | Aug-2011 | C | 4 | Added note restricting use of steel windows in humid and ESC C3-C5 locations. |
Nov-2018 | N | UFGS 08 53 00 Plastic Windows | Aug-2011 | C | 4 | Added note restricting use of plastic windows in humid and ESC C3-C5 locations. |
Nov-2018 | N | UFGS 08 71 00 Door Hardware | Feb-2016 | C | 2 | Added requirements for hinges, locks and locksets, exit devices, closers, and finishes in humid and ESC C3-C5 locations. |
Nov-2018 | N | UFGS 08 91 00 Metal [Wall] [and] [Door] Louvers | May-2011 | C | 2 | Added note for louver and finish requirements in humid and ESC C3-C5 locations. |
Nov-2018 | N | UFGS 09 22 36 Lath | Jan-2008 | C | 2 | Added requirements for accessories, hangers, and wires, in high humidity and ESC C3-C5 locations, and straps or rods in locations subject to violent storms. |
Nov-2018 | N | UFGS 09 23 00 Gypsum Plastering | Aug-2016 | C | 1 | Added mix requirement for acoustical plaster finish coat in high humidity ad ESC C3-C5 locations. |
Nov-2018 | N | UFGS 09 29 00 Gypsum Board | Aug-2016 | C | 3 | Added requirements to use PVC or plastic trim and accessories in high humidity and ESC C3-C5 locations. |
Nov-2018 | N | UFGS 09 90 00 Paints and Coatings | May-2011 | C | 4 | Added note to use UFGS 03 31 29 or UFGS 03 31 30 in ESC C4 and C5 locations or where deicing salts. |
Nov-2018 | N | UFGS 26 32 13.00 20 Single Operation Generator Sets | Aug-2018 | C | 1 | Deleted now obsolete calculation requirement for Brake Mean Effective Pressure (BMEP). |
Nov-2018 | S | UFGS 01 33 00 Submittal Procedures | Aug-2018 | C | 1 | Submittal Note updated and tailoring changes. |
Nov-2018 | S | UFGS 03 41 33 Precast Structural Pretensioned Concrete | Nov-2018 | C | 1 | Added requirement and note to use galvanized tendons in ESC C4 and C5 locations, and concrete cover requirements for tendon anchorages for post tensioning. |
Nov-2018 | S | UFGS 06 18 00 Glue-Laminated Construction | Nov-2018 | C | 1 | Added Note to not use GLC in ESC C4 and C5 and humid locations. |
Nov-2018 | S | UFGS 12 32 00 Manufactured Wood Casework | Nov-2018 | C | 1 | Added note for drawer bottoms, plastic laminate covered cabinet doors, and non-ferrous metal fasteners, fittings, and hardware. |
Feb-2019 | A | UFGS 01 50 00 Temporary Construction Facilities and Controls | May-2018 | C | 1 | Corrected spelling errors in paragraphs 2.3.1 and 2.3.2 and deleted out of place measurements below paragraph 2.3.3 in response to CCR 7090. |
Feb-2019 | A | UFGS 01 78 00 Closeout Submittals | Aug-2011 | C | 5 | Added submittal item to paragraph 1.7.1 in response to CCR 7121. |
Feb-2019 | A | UFGS 02 41 00 [Demolition] [and] [Deconstruction] | May-2010 | C | 2 | Coordinated the requirements for demolition and deconstruction activities with UFGS 01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL. |
Feb-2019 | A | UFGS 33 40 00 Storm Drainage Utilities | Feb-2010 | C | 6 | Moved the LID Verification Report to SD-11 Closeout Submittals in response to CCR 6353. |
Feb-2019 | A | UFGS 35 05 40.17 Self-Lubricated Materials, Fabrication, Handling, and Assembly | May-2014 | C | 2 | Updated Hydroelectric Design Center (HDC) phone number and ER reference in response to CCR 7048. |
Feb-2019 | S | UFGS 01 33 00 Submittal Procedures | Aug-2018 | C | 2 | In response to CCR's 7173, 7174, 7175, 7176, 7177, and 7123. 02/28/19 INTERIM RELEASE: This section was updated in response to CCR's 7314 and 7315 - the banner was incorrectly marked and was corrected to indicate Change 2; the command Execute Revisions was run to eliminate formatting elements that displayed in the previous version. |
May-2019 | N | UFGS 01 14 00 Work Restrictions | Nov-2011 | C | 7 | In response to CCR 7479, the location and phone number for SWFPAC Pass and ID office has been updated in paragraph 1.16.1.1 Vehicle Access |
May-2019 | N | UFGS 01 35 26 Governmental Safety Requirements | Nov-2015 | C | 7 | In response to CCR 7271, added language to state the District Dive Coordinator will submit documents for approval via the Contracting Officer. |
May-2019 | N | UFGS 01 57 19 Temporary Environmental Controls | Nov-2015 | C | 2 | In response to CCR 7194, FAR clause 52.242-14 Suspension of Work was added to the paragraph "Non-Compliance Notifications"; updated links per CCRs 7375 and 7376 |
May-2019 | A | UFGS 04 20 00 Unit Masonry | Nov-2015 | C | 2 | Added sentence to paragraph 2.6.2.7 in response to CCR 7025. |
May-2019 | A | UFGS 11 13 19.13 Loading Dock Levelers | Aug-2009 | C | 1 | Added reference publications MHI MH30.1, MHI MH30.3, ASTM D624, and ASTM D2632 in response to CCR 7391. |
May-2019 | A | UFGS 35 05 40.17 Self-Lubricated Materials, Fabrication, Handling, and Assembly | May-2014 | C | 3 | Updated list of allowable materials in paragraph 2.2 in response to CCR 6444, CCR 6719, and CCR 7165. |
May-2019 | S | UFGS 01 33 00 Submittal Procedures | May-2019 | C | 3 | Editing Para 1.17 |
Aug-2019 | A | UFGS 01 45 00.15 10 Resident Management System Contractor Mode (RMS CM) | Nov-2016 | C | 2 | Updated RMS requirements in paragraph 1.4 and deleted paragraph 1.5 in response to CCR 7627. |
Aug-2019 | A | UFGS 01 50 00 Temporary Construction Facilities and Controls | May-2018 | C | 2 | Added tailoring option and editor's note to paragraph 3.6 in response to CCR 7602. Added reference tags and corrected character spacing in paragraph 1.5 in response to CCR 7624. |
Aug-2019 | A | UFGS 23 52 00 Heating Boilers | Apr-2008 | C | 4 | Revised paragraph 2.12.14 in response to CCR 7344. |
Aug-2019 | N | UFGS 09 97 13.16 Interior Coating of Welded Steel Water Tanks | May-2011 | C | 2 | In response to CCR 4193, the NOTE under paragraph "SURFACE PREPARATION" (3.8) has been removed as the instructions refer to SSPC SP 12 which has been withdrawn. |
Aug-2019 | N | UFGS 01 35 13 Special Project Procedures | Nov-2011 | C | 1 | In response to CCR 6316, added paragraph to "Schedule of Work/Aircraft Operating Schedules" (3.1.2 ) to define/clarify "Existing Conditions Survey" |
Aug-2019 | N | UFGS 33 52 40 Fuel Systems Piping (Non-Hydrant) | Nov-2018 | C | 1 | Updated section to include the requirements if water is used during hydrostatic testing and/or pigging. |
Aug-2019 | N | UFGS 01 45 00.00 20 Quality Control | Nov-2011 | C | 3 | In response to CCRs 6298 and 6299, statements requiring eOMSI/OMSI were changed to bracketed options in paragraphs "Duties Statement" (1.5.2.1) and "Test Reports and Monthly Summary Report of Tests" (1.12.5), respectively. In response to CCR 6558, Specifier Note and bracketed option were added to paragraph "Requirements" (1.6.1.1), list item k. "LIST OF DEFINABLE FEATURES" |
Aug-2019 | N | UFGS 01 57 19 Temporary Environmental Controls | Nov-2015 | C | 3 | In response to the following CCRs: #5233 - revised language in paragraph "Dust Control" (3.5.7) to reflect the Crystalline Silica hazard associated with cement and concrete products per the new OSHA Standard of Crystalline Silica; #5733 - "Stormwater Pollution Prevention Plan" has been added as a submittal item under SD-01 and in paragraph "Stormwater Pollution Prevention Plan" (3.2.1.1); #7178 - revision to clarify submittal item "Solid Waste Management Report", updated as "Monthly Solid Waste Disposal Report" in Part 1 (1.11.1) and "Project Solid Waste Disposal Documentation Report" in Part 3 (3.7.2.1) and in the Submittal Article under SD-06 and SD-11 respectively; #7179 - added a new row "C&D Debris Composted" to table under paragraph Nonhazardous Solid Waste Diversion Report (3.6.2) |
Aug-2019 | N | UFGS 01 32 17.00 20 Cost-Loaded Network Analysis Schedules (NAS) | May-2018 | C | 2 | Updated section to include the required Oracle Primavera P6 software settings to be utilized in preparation and maintenance of the construction schedule and the tabular reports required to be submitted with each monthly invoice. |
Aug-2019 | N | UFGS 01 35 26 Governmental Safety Requirements | Nov-2015 | C | 8 | In response to CCR 7273, "Dive Operations Plan" has been added as a submittal item under SD-01 and in paragraph "DIVE SAFETY REQUIREMENTS" (1.19) |
Nov-2019 | A | UFGS 13 48 00 [Seismic ]Bracing for Miscellaneous Equipment | May-2018 | C | 1 | Updated paragraphs 2.2 and 2.3 in response to CCR 6932. |
Nov-2019 | A | UFGS 23 00 00 Air Supply, Distribution, Ventilation, and Exhaust Systems | Aug-2018 | C | 1 | Added bracketed statement to paragraph 2.11.2 in response to CCR 7108. Incorporated dispersal of criteria from the retired UFC 3-440-05N TROPICAL ENGINEERING, and the addition of corrosion protection criteria to coordinate with UFC 1-200-01 DoD BUILDING CODE. |
Nov-2019 | A | UFGS 23 05 48.19 [Seismic] Bracing for HVAC | May-2018 | C | 1 | Updated paragraphs 2.3, 2.4.1, and 2.5 in response to CCR 6932. |
Nov-2019 | A | UFGS 23 07 00 Thermal Insulation for Mechanical Systems | Feb-2013 | C | 5 | Incorporated dispersal of criteria from the retired UFC 3-440-05N TROPICAL ENGINEERING, and the addition of corrosion protection criteria to coordinate with UFC 1-200-01 DoD BUILDING CODE. |
Nov-2019 | A | UFGS 23 09 00 Instrumentation and Control for HVAC | Feb-2019 | C | 1 | Added new paragraph 1.1.1 to accommodate a recent change in Navy policy. |
Nov-2019 | A | UFGS 23 52 00 Heating Boilers | Apr-2008 | C | 5 | Updated designer's note on page 15 in response to CCR 6454. |
Nov-2019 | A | UFGS 26 32 15.00 10 Diesel-Generator Set Stationary 100-2500 KW, with Auxiliaries | Oct-2007 | C | 1 | Incorporated dispersal of criteria from the retired UFC 3-440-05N TROPICAL ENGINEERING, and the addition of corrosion protection criteria to coordinate with UFC 1-200-01 DoD BUILDING CODE. |
Nov-2019 | A | UFGS 26 42 14.00 10 Cathodic Protection System (Sacrificial Anode) | Aug-2008 | C | 1 | Updated paragraphs 2.3.11.3, 2.3.14, 3.5.2.1, and 3.5.2.2 to remove "brand name or approved equal" language in response to CP/DWG discussions. |