- Aesthetic Challenges
- Aesthetic Opportunities
- Air Barrier Systems in Buildings
- Assessment Tools for Accessibility
- Balancing Security/Safety and Sustainability Objectives
- Daylighting
- Designing Buildings to Resist Explosive Threats
- Electric Lighting Controls
- Electrical Safety
- Energy Analysis Tools
- Energy Codes and Standards
- Energy Efficient Lighting
- Evaluating and Selecting Green Products
- Facility Performance Evaluation (FPE)
- Glazing Hazard Mitigation
- High-Performance HVAC
- Life-Cycle Cost Analysis (LCCA)
- Materials
- Natural Ventilation
- OmniClass
- Passive Solar Heating
- Psychosocial Value of Space
- Reliability-Centered Maintenance (RCM)
- Retrofitting Existing Buildings to Resist Explosive Threats
- Seismic Design Principles
- Style
- Sun Control and Shading Devices
- Sustainable O&M Practices
- Threat/Vulnerability Assessments and Risk Analysis
- Windows and Glazing
RESOURCE PAGE
Electric Lighting Controls
Last updated: 07-23-2010
Within This Page
Introduction
Lighting controls have traditionally been used to create moods. Today, they are also used as part of a high quality energy efficient lighting system that integrates daylight and electric light sources to provide a comfortable and visually interesting environment for the occupants of a space. Electric lighting controls are appropriate for a wide variety of spaces, from restrooms to large open offices, from conference rooms to classrooms. They can be incorporated with daylighting to provide flexibility, energy savings, and ecological benefits. Although lighting controls are still most commonly used in commercial buildings, they are also increasingly being used in residential applications.
Description

Various types of occupancy sensors and photosensors
Electric lighting controls are used in lighting design projects to achieve a high quality energy efficient lighting system. Specifying a layered, daylight-integrated lighting and control system gives the occupants control of the lighting while providing appropriate lighting levels, minimizing glare, balancing surface brightness, and enhancing the surrounding architecture.
When electric lighting controls are used properly, energy will be saved and the life of lamps and ballasts can be extended. Lighting controls will help reduce energy by:
- Reducing the amount of power used during the peak demand period by automatically dimming lights or turning them off when they are not needed
- Reducing the number of hours per year that the lights are on
- Reducing internal heat gains by cutting down lighting use, which allows for reduced HVAC system size and a reduction in the building's cooling needs
- Allowing occupants to use controls to lower light levels and save energy

Example of a photosensor
There are other reasons to use electric lighting controls. For example, dimming controls can provide the lighting flexibility which is often required in multi-use rooms or rooms in which projectors are used. Exterior motion detectors and interior occupancy sensors can be used to turn lights on when people (including intruders) are present. Moreover, by tuning an environment for the individual occupant's or group's visibility, comfort and productivity can be improved.
A. Types of Lighting Controls
The most common form of electric lighting control is the on/off "toggle" switch. Other forms of lighting control include occupancy sensors, daylight sensors, clock switches, a variety of manual and automatic dimming devices, and centralized controls. Some controls operate on line-voltage power, while others are low-voltage (DC) powered. Note that fluorescent fixtures that are intended to be dimmed require special compatible dimming ballasts. Also, controls can be linked together which can perform multiple control tasks.
Standard on/off switches and relays can be used to turn groups of lights on and off together. Creative design options can be developed with this simple tool, if the circuiting is properly designed. For example, some of the lamps in each fixture can be switched together, every other fixture can be switched as a group, or lighting near the windows can be turned off when daylight is plentiful.
Occupancy sensors (including passive infrared, ultrasonic, and dual technology sensors) serve three basic functions:
- To automatically turn lights on when a room becomes occupied,
- To keep the lights on without interruption while the controlled space is occupied, and
- To turn the lights off within a preset time period after the space has been vacated.
Some sensors have settings that allow the specifier to select between the functions listed above (manual on instead of automatic on, for example). Note that sensor characteristics may vary considerably from manufacturer to manufacturer, so it is important to carefully evaluate the options for each device.
Passive infrared sensors (PIR) are triggered by the movement of a heat-emitting body through their field of view. Wall-box type PIR occupancy sensors are best suited for small, enclosed spaces such as private offices, where the sensor replaces the light switch on the wall and no extra wiring is required. PIR sensors cannot "see" through opaque walls, partitions, or windows so occupants must be in direct line-of-site of the sensor.
Ultrasonic sensors emit an inaudible sound pattern that is disrupted by any moving object altering the signal returning to the sensor (Doppler shift). They are best suited for spaces where line-of-sight view to the occupant is not always available. This type of sensor detects very minor motion better than most infrared sensors and is often used in restrooms since the hard surfaces will reflect the sound pattern.
Dual-technology occupancy sensors use both passive infrared and ultrasonic technologies for less risk of false triggering (lights coming on when the space is unoccupied). Combining the technologies requires a more reliable, yet slightly larger and more expensive device.

Example of a ceiling-mounted occupancy sensor
Occupancy sensor placement is very important to the successful implementation of the control design intent. Occupancy sensors must be located to ensure that they will not detect movement outside of the desired coverage area, through an open doorway, for example. Ultrasonic devices are sensitive to air movement and should not be placed near an HVAC diffuser, where air movement may cause false tripping.
Occupancy controls can be used in conjunction with dimming or daylight controls to keep the lights from turning completely off when a space is unoccupied, or to keep the lights off when daylight is plentiful and the room is occupied. This control scheme may be appropriate when occupancy sensors control separate groups of luminaires, or "zones", in a large space, such as in a laboratory or an open office area. In these situations, the lights can be dimmed to a predetermined level in one specific area when the space is unoccupied.
There are several different kinds of coverage patterns and mounting configurations for occupancy sensors, such as:
- Ceiling-mounted controls with 360° coverage
- Ceiling-mounted controls with elongated "corridor" coverage
- Wall-mounted controls with a fan-shaped coverage pattern
- Ceiling-mounted controls with a rectangular coverage pattern
- and more!
Additionally, take note of the difference between each device's sensitivity to minor motion (working at a desk) vs. major motion (walking or half-step activity). The sensor manufacturer should provide coverage diagrams for both levels of activity. HID lamps do not work well with occupancy sensors because most HID lamps take a long time to start each time they are switched off.
Additional Occupancy Sensor Information
- "Advanced Lighting Guidelines: 2003 Edition", New Buildings Institute
- Hubbell, Inc.—Sensor Products
- "Occupancy Sensors", (PDF 402 KB, 40 pgs) NLPIP Specifier Reports, Vol. 5, No. 1, October 1998.
- Watt Stopper/Legrand®—Occupancy Sensor Products
Manual dimming gives occupants of a space an added degree of control and satisfaction, as well as an opportunity to save energy. It provides users with the flexibility to instantly change the characteristics of a space to make it a more comfortable and productive environment. There are several families of manual preset dimming control.
- Manual hard-wired control
- Preset scene control
- Remote infrared control
- Remote radio frequency control
Manual hard-wired control consists of a dimmer, connected to a single luminaire or zone which is operated by the user at the device. Preset scene dimming controls change the light level settings for multiple zones simultaneously at the press of a button.
Remote control dimming is another form of manual dimming that is well suited for retrofit projects to minimize rewiring. Infrared and radio frequency technologies are most successful in these applications. Remote infrared control operates in a similar fashion to other infrared technologies like television, for example. Radio frequency controls are equipped with a sender that "talks" to other dimmer's receivers. This allows multi-zone control from a single-zone device. Personal control systems are now available that allow users to change levels of lighting, sound, heating/cooling, etc., in their own workspaces. See also WBDG Productive—Design for the Changing Workplace.
Additional Personal Control Systems Information
- Johnson Controls Personal Environments®
- Lutron GRAFIK Eye 3000—Preset Lighting Controls
- Watt Stopper/Legrand®—Remote Control Lighting Products

Left and Center: Lutron's GRAFIK preset lighting controls. Photos courtesy of Lutron.
Right: Photosensor. Photo courtesy of Intelligent Lighting Controls, Inc.
Light-level sensors or photosensors can be used to automatically turn lights on or off, or dim them, depending on the available daylight available in the space. Daylight dimming can maintain the desired light level while providing a smooth, barely noticeable transition to or from electric lighting as daylight increases or decreases.
Additional Photosensor Information
- "Advanced Lighting Guidelines: 2003 Edition", New Buildings Institute
- "Photosensors," (PDF 267 KB, 20 pgs) NLPIP Specifier Reports, Vol. 6, No. 1, March 1998.
- Photosensor Tutorial, Lighting Research Center
- Watt Stopper/Legrand®—Daylighting Controls
Clock switches turn lights on or off for a specific period of time. They are especially useful for turning off photocell-activated exterior lighting late at night (as long as that lighting is not needed after a certain time).
Centralized controls can be used to automatically turn on, turn off, and/or dim lighting at specific times or under certain load conditions. This type of control can be used in a conference room or on a building-wide scale. Centralized control strategies can also integrate lighting controls with other building systems such as mechanical or security systems.
Distributed controls are based on digital communication protocols. These systems are local, or integral, to the luminaire itself, not housed in a central cabinet or enclosure. They integrate with building automation or energy management system. A Digital Addressable Lighting Interface (DALI) system provides a means of control which can speak to an individual ballast or groups of ballasts. The "control wiring" is independent of the "power wiring" and provides the highest degree of flexibility available at this time. When space configuration or occupant needs change, the system can respond by reassigning the ballasts accordingly.
B. Selecting the Appropriate Lighting Controls
There are many guides and services available for designing lighting control systems. Some controls manufacturers will actually do a controls layout on the building plans or even on electronic drawing files, free of charge or for a nominal fee. If you prefer to do the controls layout yourself, it is advisable that you provide a written "sequence of control" which describes the design intent and a "performance specification" which describes the performance characteristics of individual components. Further, some coordination with the selected controls manufacturer will help to avoid surprises during construction and commissioning.
If you know how you would like the controls scheme to work, but you are not sure what equipment to choose or how it should be connected electrically, explain your ideas to the manufacturer's technical support personnel. Chances are they will be able to help you work out the details.
The table below provides control ideas for several different room types and usage patterns. Some additional links to help on manufacturers' web sites are provided below the table.
| Space Type | Typical Use Pattern | If... | Then... |
|---|---|---|---|
| Cafeterias or Lunchrooms | Occasionally occupied | Daylighted | Consider daylight-driven dimming or on/off control |
| Occupied occasionally | Consider ceiling-mounted occupancy sensor(s). Make sure minor motion will be detected in all desired locations. | ||
| Classroom | Usually occupied | Multiple tasks like overhead projectors, chalkboard, student note taking and reading, class demonstrations | Consider manual dimming |
| Occasionally occupied | Occupied by different groups of students and teachers daily | Consider ceiling- or wall-mounted occupancy sensor(s) and manual dimming. Make sure that minor motion will be detected. | |
| Lights left on after hours | Consider centralized controls and/or occupancy sensors. | ||
| Computer Room | Usually unoccupied | Lights are left on all the time | Consider occupancy sensors with manual dimming. Be sure that minor motion will be detected and that equipment vibration will not falsely trigger the sensor. |
| Conference Room | Occasionally occupied | Multi-tasks from video-conferencing to presentations | Consider manual dimming (possibly preset scene control) |
| Small conference room | Consider a wall box occupancy sensor | ||
| Large conference room | Consider ceiling- or wall-mounted occupancy sensor(s). Be sure that minor motion will be detected in all desired locations. | ||
| Gymnasium or Fitness | Usually occupied | Requires varied lighting levels for activities | Consider manual dimming and occupancy sensors. Be sure that the HVAC system will not falsely trigger the sensor. |
| Occasionally occupied | Requires varied lighting levels for activities | Consider ceiling- and wall-mounted passive infrared occupancy sensors. Be sure that the coverage areas of the sensors are sufficiently overlapped to keep the lights on when the room is occupied. | |
| Hallways | Any | Occasionally or usually occupied | Consider occupancy sensors with elongated throw. Be sure that coverage does not extend beyond the desired area. |
| Daylighted | Consider daylight on/off control. | ||
| Health Care—Examination Rooms | Occasionally occupied | Different lighting needs for examination | Consider manual dimming. |
| Small areas | Consider a wall box occupancy sensor. | ||
| Health Care—Hallways | Usually occupied | Daylighted | Consider automatic daylight-driven dimming. |
| Requires lower lighting level at night | Consider centralized controls to lower lighting levels at night. | ||
| Health Care—Patient Rooms | Usually occupied | Different lighting needs for watching television, reading, sleeping, and examination | Consider manual dimming. Occupancy sensors may not be appropriate. |
| Hotel Rooms | Occasionally occupied | Used primarily in the late afternoon through evening for sleeping and relaxing | Consider manual dimming. |
| Laboratories | Usually occupied | Daylighted | Consider automatic daylight-driven dimming in combination with occupancy sensors. |
| Laundry Rooms | Occasionally occupied | Requires high light levels, yet lights are usually left on | Consider occupancy sensors. |
| Libraries—Reading Areas | Usually occupied | Daylighted | Consider automatic daylight-driven dimming. Occupancy sensors may be appropriate. |
| Lights left on after hours | Consider centralized controls. | ||
| Libraries—Stack Areas | Occasionally occupied | Stacks are usually unoccupied | Consider ceiling-mounted sensor(s). |
| Lobby or Atrium | Usually occupied but no one "owns" the space | Daylighted and lights should always appear on | Consider automatic daylight-driven dimming. |
| It isn't a problem if lights go completely off in high daylight | Consider automatic daylight-driven dimming or on/off control. | ||
| Lights are left on all night long, even when no one is in the area for long periods | Consider occupancy sensors. Be sure that minor motion will be detected in all desired areas. | ||
| Office, Open | Usually occupied | Daylighted | Consider automatic daylight-driven dimming. |
| Varied tasks from computer usage to reading | Consider manual dimming. | ||
| Lights left on after hours | Consider centralized controls and/or occupancy sensors. | ||
| Office, Private | Primarily one person, coming and going | Daylighted | Consider manual dimming, automatic daylight-driven dimming, or automatic on/off. |
| Occupants are likely to leave lights on and occupants would be in direct view of a wall box sensor | Consider a wall box occupancy sensor. Add dimming capabilities if appropriate. | ||
| Occupants are likely to leave lights on and partitions or objects could hide an occupant from the sensor | Consider a ceiling- or wall-mounted occupancy sensor. Add dimming capabilities if appropriate. | ||
| Photocopying, Sorting, Assembling | Occasionally occupied | Lights are left on when they are not needed | Consider an occupancy sensor. Be sure that machine vibration will not falsely trigger the sensor. |
| Restaurant | Usually occupied | Daylighted | Consider automatic daylight-driven dimming. |
| Requires different lighting levels throughout the day | Consider manual dimming (possibly preset scene dimming). | ||
| Requires different lighting levels for cleaning | Consider centralized control. | ||
| Restroom | Any | Has stalls | Consider a ceiling-mounted ultrasonic occupancy sensor for full coverage. |
| Single toilet (no partitions) | Consider a wall switch occupancy sensor. | ||
| Retail Store | Usually occupied | Daylighted | Consider automatic daylight-driven dimming |
| Different lighting needs for retail sales, stocking, cleaning | Consider centralized controls or preset scene dimming control. | ||
| Warehouse | Aisles are usually unoccupied | Daylighted | Consider daylight-driven dimming or daylight on/off control. |
| Lights in an aisle can be turned off when the aisle is unoccupied | Consider ceiling-mounted occupancy sensors with elongated throw. Select a sensor that will not detect motion in neighboring aisles, even when shelves are lightly loaded. |
Additional Controls Design and Selection Links
- "Advanced Lighting Guidelines: 2003 Edition", New Buildings Institute
- Hubbell Inc.—Occupancy Sensor Guide
- Watt Stopper/Legrand®—Products and Solutions
C. Commissioning of Lighting Control Systems
It cannot be understated how important commissioning is to the ultimate success of a lighting control system. If a lighting control system is not commissioned, it may result in greater energy consumption than a building without any controls at all.
Commissioning is defined as the final adjustment, calibration, and tuning of the various components after they have been installed and the space is occupied. This process requires the participation of the building owner, a commissioning agent, the lighting designer, the electrical engineer, a manufacturer's representative, and building maintenance personnel.
Commissioning activities will vary from space to space. They can range from simply "burning in" fluorescent lamps that are to be dimmed to configuring software to respond to weekday, weekend, and holiday occupancy schedules.
Commissioning is often considered impractical, too burdensome, or costly. However, manufacturers of lighting controls are continuously improving their devices to help simplify and expedite the process. When commissioning is completed, the building maintenance personnel must be provided with all relevant documentation required for the ongoing maintenance of the lighting control system.
D. Economic Analysis of Lighting Control Systems
Lighting controls are cost-effective, especially when one considers long-term life-cycle costs along with initial costs. Lighting controls can add approximately $0.50-$1.00 per square foot initially. Payback periods vary widely by project and are difficult, at best, to predict accurately. That does not take into account the savings from reduced energy use and HVAC reduction.
The easiest way to do an economic analysis of lighting controls is to use an "effective energy charge (EEC)," which is a cost per kWh number derived by dividing the entire electricity bill (in dollars) by the total amount of energy used during that billing period (in kWh). The potential savings per controlled fixture is calculated as follows:
$ Savings per year = ([Wb x HPYb x PFb] — [Wf x HPYf x PFf]) * (EEC) * (1 kWatt/ 1000 Watts)
Where:
Wb is the baseline watts of the controlled fixture(s)
HPYb is the baseline number of hours per year that the fixture is on
PFb is the baseline power fraction for the fixture or fixtures (use 1 for full power)
Wf is the final watts of the controlled fixture(s) (i.e. after retrofit or redesign)
HPYf is the final number of hours per year that the fixture is on (i.e. after controls are installed that turn the lights off when they are not needed, such as occupancy sensors or centralized controls)
PFf is the final power fraction for the fixture(s) (i.e. if a fixture will be dimmed to an annual average of 50%, use .5. For low dimming levels, the energy usage fraction is slightly higher than the dimming percentage due to ballast losses.)
EEC is the "effective energy charge" in $/kWh.
This method of calculating annual dollar savings is an approximate estimate because is does not allow you to calculate the exact changes in demand charges—demand charges have been wrapped up into the "effective energy charge."
Application
Electric lighting controls can be used in all types of buildings and spaces. Some case studies are detailed below:
- Education: Multimedia Classroom, University of Toronto, Toronto, Ontario, Canada
Pre-set dimming controls - Health Care Facility: Way Station Club House, Frederick, MD
Integrated daylighting and occupancy sensors. To achieve the design goals, the Way Station team demonstrated creativity and excellent technical competence. - Office Building: Port of Seattle Headquarters, Seattle, WA
Integrated daylighting, two large atria with photocell controls, partition mounted indirect fluorescent lighting, and separate perimeter controls - Retail: Wal-Mart, City of Industry, CA
Integrated daylight, photo-sensors, and automatic continuous fluorescent dimming
Relevant Codes and Standards
Federal Mandates
- Energy Performance Standards (10 CFR part 435)
- Energy Policy Act of 2005 (PDF 1.9 MB, 550 pgs)
Federal Criteria
Standards
- ASHRAE/IESNA Standard 90.1 Energy Standard for Buildings Except Low-Rise Residential Buildings
- IESNA Lighting Handbook, 9th Edition
- IESNA Recommended Practice RP-1, Office Lighting
- IESNA Recommended Practice RP-16, Nomenclature and Definitions for Illumination Engineering
Additional Resources
WBDG
Building / Space Types
Applicable and relevant to all building types and space types.
Design Objectives
Aesthetics, Cost-Effective, Functional / Operational, Historic Preservation—Update Building Systems Appropriately, Productive—Provide Comfortable Environments, Secure / Safe, Sustainable—Optimize Energy Use, Sustainable—Enhance Indoor Environmental Quality, Sustainable—Optimize Operational and Maintenance Practices
Products and Systems
Federal Green Construction Guide for Specifiers:
Project Management
Building Commissioning, Project Planning, Delivery and Controls
Federal Programs and Services
- Defense Logistics Agency, Defense Supply Center Philadelphia (DSCP)—Manages all energy-efficient lighting products for the entire Federal Government. Phone: (800) DLA-BULB
- Energy Star® Program
- FEMP Energy-Efficient Products, Energy Efficiency Recommendations, Lighting Technologies—Contains recommendations on lighting technologies, including fluorescent luminaires, and selecting lighting controls for offices and public buildings
- GSA Federal Acquisition Service
- Lawrence Berkeley National Laboratory—Lighting Research Group
Products Manufacturers and Suppliers
- AC Electronics
- Advance Transformer Company
- Cooper Controls
- GE Company—Lighting Control
- GSA Federal Acquisition Service
- HUNT Dimming
- Intelligent Lighting Controls, Inc.
- Lehigh Electric Products Co.
- Leviton Manufacturing Co., Inc.
- Lightolier Controls
- Lithonia Lighting
- Lutron
- Osram Sylvania
- Pass & Seymour/Legrand
- Sensor Switch, Inc.
- Tensor Technologies Corporation
- Touch-Plate Lighting Controls
- Tridonic Atco Group
- Watt Stopper/Legrand®
Organizations/Associations
- Illuminating Engineering Society of North America (IESNA)
- International Association for Energy Efficient Lighting (IAEEL)
- International Association of Lighting Designers (IALD)
- Lighting Controls Association
- National Association of Energy Service Companies(NAESCO)
- National Electrical Manufacturers Association (NEMA)
- National Lighting Bureau "High-Benefit Lighting"
- New Buildings Institute (NBI)
Publications
- "Advanced Lighting Guidelines: 2003 Edition", New Buildings Institute
- The Architect's Guide to Energy Conserving Products and Systems
- Architectural Graphic Standards (AGS), 11th Edition
by John Wiley & Sons, Inc.: The American Institute of Architects, March 2007.
- E Source Emerging Technology SeriesE Source
- Emerging Technology Series (available with membership only)—
- New Dimming Controls: Taking it Personally, ER-00-13
- Practical Control Strategies for Harvesting Daylight Savings, ER-00-6
- Public Interest Energy Research (PIER) Program—Technical briefs available free of charge made possible by California Energy Commission's PIER program.
- TI 811-16 Lighting Design
- UFGS 26 51 00 Interior Lighting
Others
- California Lighting Technology Center, University of California, Davis
- Lighting Research Center (LRC), School of Architecture, Rensselaer Polytechnic Institute
- National Lighting Products Information Program